Smoke Test
TURN OFF Logic Sens - Dip switch 10
Smoke end cap if there is a response within:-
60 seconds - A type
90 seconds - B type
120 seconds - C type
then you are ok to normalise.
REMEMBER - TURN Logic Sens back on
It may not go into fire when smoking end cap as this is testing system is clear of blockages / breakages.
If you wish to check it will go into fire you can take cover off unit and smoke it there.