Smoke Test

Created by Sally Ryder, Modified on Fri, 26 Jan, 2024 at 1:01 PM by Sally Ryder

Smoke Test

TURN OFF Logic Sens - Dip switch 10

Smoke end cap if there is a response within:-
60 seconds - A type
90 seconds - B type
120 seconds - C type
then you are ok to normalise.


REMEMBER - TURN Logic Sens back on


It may not go into fire when smoking end cap as this is testing system is clear of blockages / breakages.


If you wish to check it will go into fire you can take cover off unit and smoke it there.